Research paper · Efficiency · Complex Data Analytics · October 2026 · v1

Feature-based grouped autoencoders for low-cost fault detection on rotating machinery

Yannis Fus

Key result

Grouped autoencoders on 37 engineered features catch all 15 faults (median 36 s, no false alarms) at 1,312 MACs per second, versus 6 of 15 at 1.06 M MACs for a raw-sample autoencoder.

MethodMetricValueCost
Autoencoder on raw samplesFaults caught6 / 151,060,864 MACs
Isolation forest, 37 featuresFaults caught6 / 15—
PCA, 37 featuresFaults caught9 / 15—
Grouped autoencoders (this paper)Faults caught15 / 151,312 MACs

Introduction

Autoencoders are a common choice for unsupervised fault detection on machines: train on normal operation, then alarm when reconstruction error rises. Applied directly to raw sensor samples, they are expensive and, as we show here, not very good at it.

We study what actually improves an autoencoder detector on a variable-speed pump station with 15 gradually developing faults. Four choices matter, and none of them is a larger network:

  1. Engineered features instead of raw samples
  2. Residuals scored in units of their own noise
  3. One small model per physical subsystem
  4. Gating during speed transients, with calibration data that covers the operating envelope

Together they raise detection from 6 to 15 of 15 faults, with no false alarms in 3.25 hours of normal operation. They also cut model arithmetic by a factor of 808.

Benchmark

The test bench is a simulated centrifugal pump station. Because it is simulated, the true onset of every fault is known to the second. This is also the main limitation of the study (see Limitations).

SignalRateNormal behaviour
Vibration, drive end and non-drive end1 kHzShaft orders (1×, 2×, 6× vane pass), a 380 Hz structural resonance and noise; amplitude grows with speed
Speed10 HzFour setpoints from 1,200 to 2,950 rpm, 20 s ramps, held 3 to 15 min
Pressure10 HzPump affinity law: rises with speed squared, falls as the valve opens
Motor current10 HzRises with speed cubed and with load
Temperature10 HzFollows current with a 10-minute thermal lag

An unmeasured valve wanders slowly, so the same speed produces a range of pressures and currents. That defeats fixed limits on single signals.

Five fault types, three of each, are spread over a 6-hour test stream. Each ramps up from zero, so detection delay is meaningful:

FaultWhat changesOnset ramp
Bearing outer raceImpacts at 3.57 × shaft speed exciting a 300 Hz resonance5 min
Imbalance1× vibration grows to twice its normal level2 min
CavitationBroadband vibration above 200 Hz; pressure becomes noisy and drops 5 %20 s
Clogged impellerCurrent rises 8 % while pressure stays normal1 min
Pressure sensor driftReading rises by 0.4 bar; nothing physical changes5 min

Protocol. All detectors train on 8 hours of normal operation. Each threshold is set 5 % above the highest value its alarm statistic reaches on 3 further hours of normal data. A fault counts as detected when an alarm fires during it. Delay runs from the true onset to the end of the first alarming window. False alarms are alarm starts during 3.25 hours of normal test operation, excluding one minute after each repaired fault.

Method

Features. Each 1-second window is reduced to 37 engineered features: shaft-order amplitudes, band energies and a bearing envelope for the two vibration channels (32 features), plus window means of the process signals. The raw-sample baseline sees 2,040 values per window instead.

Normalised residuals. Squared error weighs every feature equally, so 32 noisy vibration features drown 3 precise process ones. Each residual is therefore divided by its spread σi\sigma_i on normal data:

ri=xi−x^iσir_i = \frac{x_i - \hat{x}_i}{\sigma_i}

and the window score is built from the squared rir_i.

Grouped models. The vibration features and the process signals each get their own autoencoder. The process model has 3 inputs and a 2-unit bottleneck, matching the two degrees of freedom that drive normal operation: speed and valve opening. A broken relationship between pressure, current and speed then has nowhere to hide.

Transient gating. Averaged over a window in which the speed is changing, pressure and current do not follow the steady-state laws. The process model is therefore held while the speed changes and for 30 s afterwards.

Smoothing. The alarm statistic is an exponentially weighted moving average of the log score sts_t, with weight λ=0.3\lambda = 0.3:

St=λlog⁡st+(1−λ) St−1S_t = \lambda \log s_t + (1 - \lambda)\, S_{t-1}

Results

Faults detected by each detector, out of 15
Faults detected out of 15. The last three bars add one change each to the 37-feature autoencoder.

Representation matters more than the model. On raw samples the autoencoder spends its capacity reproducing waveform phase, which says nothing about health. It catches 6 faults, the same as an isolation forest, and fewer than PCA on engineered features (9).

The single 37-feature autoencoder catches every vibration fault and none of the process faults. Clog and drift change no single signal beyond its normal range; they break a relationship between signals. The table compares it with the final detector:

FaultSingle autoencoder, 37 featuresFinal grouped detector
Cavitation3 of 3, median 16 s3 of 3, median 16 s
Pressure sensor drift0 of 33 of 3, median 36 s
Clogged impeller0 of 33 of 3, median 21 s
Imbalance3 of 3, median 78 s3 of 3, median 54 s
Bearing outer race3 of 3, median 114 s3 of 3, median 137 s

Normalised residuals leave detection at 9 of 15 but cut the median delay from 78 s to 56 s. Grouped models take it to 11. The last four faults need the operating-state fix, and the calibration amount turns out to matter as much as the gating:

Calibration dataProcess model during rampsFaults caughtMedian delayFalse alarms
3 hheld1536 s0
3 hactive1158 s0
1 hheld1515 s62
1 hactive1554 s13

Gating lets the threshold fall to where clog and drift show. That lower threshold is only safe if calibration has seen the whole envelope: one hour of data rarely visited the extreme valve positions, and the gated model fired 62 times at operating points that were normal but unfamiliar.

Severity at first alarm. Faults ramp from zero, so the useful measure of reaction is how far a fault has developed when the alarm fires:

FaultOnset rampMedian first alarmSeverity at first alarm
Pressure sensor drift300 s36 s12 % (0.05 bar)
Clogged impeller60 s21 s35 %
Imbalance120 s54 s45 %
Bearing outer race300 s137 s46 %
Cavitation20 s16 s80 %

The sensor drift is caught at a bias of about 0.05 bar, under 1 % of the pressure range and less than twice the 0.03 bar noise of a single reading.

Cost

The feature route uses 808 times less model arithmetic than the raw-sample autoencoder and trains in 4.8 s instead of 98.9 s. The vibration model can be shrunk well below its starting size:

Vibration model layersMACs, both modelsParametersFaults caughtFalse alarms
32-64-16-64-326,3046,517152
32-32-8-32-322,7202,861151
32-16-4-16-32 (chosen)1,3121,417150
32-8-3-8-32720808150
32-4-2-4-32432511150

The largest model is the only one with false alarms: a wide bottleneck learns to reproduce unusual inputs too, so its threshold must sit higher.

Quantisation has to follow the signal being protected. With int8 weights for the vibration model and int16 for the process model, the detector fits in 1,614 bytes and still catches 15 of 15 (median 38 s, no false alarms). Int8 everywhere drops to 13 of 15, because the process model must resolve 0.03 bar of noise on a 6 bar range.

At the edge, the 37 features are 148 bytes per second against 8,160 for the raw signals, 55 times less data leaving the machine.

Limitations

  • Synthetic data. All results come from a simulator whose fault models we wrote. They show which design choices matter, not how the detector performs on a real machine. A run on a public benchmark is needed before these numbers can be compared with published work.
  • No published baselines. The baselines (isolation forest, PCA, raw-sample autoencoder) were implemented and run by us on the same data, not taken from the literature.
  • One untraced anomaly. Overlapping 1-second windows with a 0.5 s hop raised 8 false alarms, against none for non-overlapping windows. The cause has not yet been found.

Reproducing the results

The code is plain Python (NumPy, SciPy, pandas, scikit-learn) with no deep-learning framework, so every multiply-accumulate is visible. simulate.py builds the data: 8 h training, 3 h calibration and 6 h test. experiments.py reproduces every number in this paper in under 15 minutes on two cores.

Reproducibility

Dataset
Synthetic variable-speed pump station (synther-anomaly-ae simulator) · v1
Hardware
2 CPU cores
Runtime
Under 15 minutes
Reproduce with
python experiments.py

Cite this

@misc{fus2026anomaly,
  title  = {Feature-based grouped autoencoders for low-cost fault detection on rotating machinery},
  author = {Fus, Yannis},
  year   = {2026},
  note   = {Synther Research}
}

Changelog

Changelog

  1. v1October 2026First publication